Distribution Center - Chicago, Illinois

Cambridge Space Heaters vs. Direct Fired Recirculation
Comparative Case Study

Download Case Study PDF

Cambridge Space Heaters

Operating Costs

Based on 4,913 Heating Degree Days @ 60°
$0.11/ft2 Gas cost @ $1.00/therm
$0.01/ft2 Electric cost @ $0.08/Kwh

$0.12/ft2 Total cost

Building Specifications

  • 999,700 ft2 x 35’ high
  • R-14 Roof / R-10 Wall

Heating System

  • (8) Cambridge Space Heaters
  • 16,192 MBH total
  • 81,920 CFM
  • 60 HP total - intermittent

Direct Fired Recirculation 

Operating Costs

Based on 4,913 Heating Degree Days @ 60°
$0.37/ft2 Gas cost @ $1.00/therm
$0.05/ft2 Electric cost @ $0.08/Kwh

$0.42/ft2 Total cost

Building Specifications

  • 814,848 ft2 x 37’ high
  • R-14 Roof / R-10 Walls

Heating System

  • (4) Direct Fired Recirculation
  • 23,548 MBH total
  • 215,000 CFM
  • 120 HP total – continuous

Summary

The Cambridge system used over 71% less total energy with less temperature variation. If the 814,848 ft2 facility had installed a Cambridge system they could have saved approximately $244,000/year operating at $0.12/ft2  vs. $0.42/ft2.